• Product information

    Measuring and control equipment

  • PC DYNAMICS pH/Redox
  • with dinodos Easy on wall-mounting plate
  • with filter/heating control Measuring, regulating, dosing
  • Art. no.: 0133-210-93



 

Description

Microprocessor-controlled measuring and control device, optionally for redox / pH or Poolcare (time-controlled) / pH, in splash-proof plastic housing, wired ready for connection 230V/50Hz. Display of measuring values on backlit graphical display with alphanumeric characters. Menu navigation via clear text display with selection of the desired language. Operating status, warning and alarm messages in clear text via the status bar on the display.

Compact measuring and control device for the measuring options:

  • ORP, pH, temperature and sample water deficiency
  • Poolcare (time-controlled), pH, temperature and sample water deficiency

Free switching between measurement options.

By adding the "potentiostatic measuring board for the Poolcontrol DYNAMICS", it is possible to implement additional measuring options.

Characteristics of system unit in wall-mounted case for disinfection and dosing equipment:

  • Microprocessor-controlled measuring and control device
  • IP 65
  • Clear graphics display
  • Logical menu structure for an easy adjustment of setpoints, limit values and parameters
  • Configuration menu for selection of measurement technology and other functions
  • Password protection to prevent unauthorized operation
  • Multilingual system / language selection
  • Measuring input for measurement of ORP
  • Measuring input for measurement of pH
  • Measuring input temperature measurement
  • Integrated standard controls for disinfection, pH correction
  • pH reduce and pH raise can be connected simultaneously
  • Control of pH raise or flocculant dosing optional
  • Automatic switch-on delay
  • Sample water monitoring
  • Dosing time monitoring
  • Empty warning contact for container fill level
  • Integrated alarm relay
  • Interfaces for connection to dinowin and dinotecNET+
  • Analog output for output of hygiene parameters

Closed, pressure-proof compact measuring cell made of transparent plastic on white PVC plate, for measurement of redox and pH.
The measuring cell includes a sample water monitoring feature. The measuring water supply is controlled via an additional ball valve. Integrated flow control monitoring module for connection to the measuring device. Return of the sample water into the water circulation is planned.

The fiber filter is used to retain impurities in the sample water to prevent entry in the measuring cell.

Fiber filter with transparent filter cup and cleanable strainer, small mesh size, standardized connections for installation in front of a measuring cell.

Measuring accessories for measurement of the parameters redox and pH.
This includes:

  • 1x redox measuring probe without reference system
  • 1x pH measuring probe
  • 1 x cleaning material liquid
  • 1 x special cleaning paste
  • 1 x calibration solution pH 4.0/50 ml
  • 1 x calibration solution pH 7.0/50 ml

Microprocessor-controlled peristaltic dosing pump for an automatic addition of any kind of liquid media. With gear motor, ball bearing rotor axis and infinitely variable digital speed control. Continuous operation with applied mains voltage.
The delivery rate is adjustable via the speed control and by means of different pump hose sizes. With integrated dosing pump hose and hose connector.

 

Technical data

System enclosure: Plastic housing, degree of protection: IP 65
System enclosure dimensions: 260 x 260 x 85 mm (W x H x D)
Weight: approx. 1.5 kg
Mains voltage: 115 / 230 V/AC, 48-63 Hz
Power consumption: 10 VA (without metering technology)
Display: via large-area graphical display 100 x 30mm
Operation: Plain text menu with buttons
Language: Language selection
Operating temperature: 5 to +40 °C
Storage temperature: -20 to +65 °C
Rel. humidity: max. 90% at 40 C°, non-condensing
Safety monitoring:
  • Input dosing stop (e.g. flow sensor)
  • Monitoring measuring water flow
  • Collective alarm / alarm relay
  • Alarm display on the screen in plain text
  • Flashing display illumination to indicate an alarm condition
  • Dosing time monitoring
Interfaces:
 
RS 485: for connection to dinowin / Profibus gateway / etc.
dinotecNET+: for connection to dinotecNET+ as a field device
Redox measuring amplifier:
 
Measuring range: -1500mV to +1500mV
Resolution: 1 mV
Ambient temperature influence: 50ppm/K (12mV)
Reference temperature: 23 °C
Input resistance: > 1012 Ohm
Redox measurement: via dip-type measuring chain without drainage system
Calibration: not required
pH measuring value amplifier:
 
Measuring range: -1500mV to +1500mV
Resolution: 0.01 pH or 1 mV
Ambient temperature influence: 50ppm/K (12mV)
Reference temperature: 23 °C
Input resistance: 1012 Ohm
Calibration pH: Optional one-point or two-point calibration
Electrode test: automatically after calibration
Temperature compensation of the pH value: can be set automatically or manually via PT1000
Temperature:
 
Temperature input for sensor: PT1000
Measurement range: 0 to +60 °C (+/-1%)
Inputs/outputs, control behaviour:
 
Control response: Selectable P, PI or PID control
Control: Optional 1-point or 2-point control
Binary outputs: 4 volt-free output relays for chlorine, lower pH and raise pH (pulse length, pulse frequency, on/off), alarm
Alternatively to raising pH: Flocculation dosing On/Off
Maximum contact load (230V AC): 370W (inductive), 500W (resistive load)
Maximum switching current: 30V/10A, 115V/0.3A, 230V/0.12A
Digital inputs: Empty alarm chlorine, pH lowering, dosing stop
Analogue output: 0(4)-20mA for single measured value (optional)
Conductor cross-section terminal block: 0.25 - 2.5mm²

Flow valve

Threaded connection for measuring probes: PG 13.5
Flow monitoring module: Reed contact with 2-wire cable connection
Min. initial pressure: 0.2 bar
Max. counter pressure: 1 bar
Sample water requirements: 120 l/h
Connection supply and drain: sample water hose 6/8mm
Material: Acrylic glass, clear, with wall mount
Dimensions (mm): 70 x 290 x 75 (wxhxd)

Fibre filter

Holder made of PP black
Filter cup made of PA transparent
Inlet/outlet ¼“ inside
Operating pressure max. 8 bar
Operating temperature min. 0°C to max. 50°C
Mesh size 0.25mm
Dimensions: 58 x 58 x135mm (wxdxh)
Weight Approx. 0.15 kg

Measuring accessories

Operating temperature: 0 to +45°C
Storage temperature: +20 to +65°C
Rel. humidity: max. 90% at 40°C, non-condensing

dinodos EASY

Mains voltage: 230V +/-10 %, 50/60Hz
Power consumption: approx. 5 VA max.
Protection class: IP 65
Dimensions housing (w x h x d): approx. 135 x 65 x 85 mm
Weight: approx. 0.6 kg
Permissible ambient temperature: +10 to +50 oC
Drive: Gear motor
Pump hose: compl. with connection pieces for suction line D4
Capacity max.: approx. 0.25-4.5 l/h (infinitely variable), at a counterpressure of max. 1.5 bar
Suction lift max.: 1.80 m
Operation: Capacity adjustable via potentiometer

 

Application

For water treatment in swimming pools, hot tubs and the like.

 

 

 

 

 

 

 

Spare parts

0101-013-00

Reed contact float, red

for inline system chlorine

 

0101-120-00

Fibre filter 3/4", connection 8/6mm

with slotted tube 0.5 mm

double-sided hose connection 8/6mm

 

0101-139-00

pH 4.0 buffer solution 50 ml

 

0101-140-00

pH 7.0 buffer solution 50ml

 

0101-158-00

GRP connector nipple 1/4 x 8/6mm

Straight version, for measuring water, with union nut

 

0111-103-00

Rx electrode without lead-out system

for dsc compact systems

and Poolcontrol 1000/S/avant

 

0161-101-01

pH combination electrode (standard), WE/S

for all measuring and control instruments

 

0181-109-00

Measuring cable for measuring electrodes (standard)

pH and redox, length: 1.2 m

 

0181-109-05

Measuring cable, with integr. reference cable

for potentiometric measurements (chlorine, ozone, pool care),

with plug, length 1.2 m

 

0181-178-01

Ball valve R 1/4" female/male, PVC

for measurement water sampling, etc.

 

0181-184-01

Special liquid cleaner for all measuring electrodes

 

0181-185-00

Special cleaning paste

for the precious metal ring on the electrodes

 

0284-025-00

Injection valve, DN 4, R 1/4", 30 mm, PVC

Hose connection 4/6 mm

 

0284-098-00

Flexible suction line, with cover fitting MÜ 61

without float switch, ball non-return valve and plug

Hose 6/4 mm, DN 4, hose length 1.5 m, for dinodos easy, START, Concept pumps

 

  •